Pro-line, Setting the Standard!

Did you pick problem "C" as the most serious?
Using our IEEE/ANSI based standards Pro-Line's analysis is quite different!


A
4.8 degrees centigrade
rise over ambient
at 30 amps (20%) Load


CRITICAL


B
19.8 degrees centigrade
rise over ambient
at 72 amps (48%) Load

CRITICAL

C
34.4 degrees centigrade
rise over ambient
at 90 amps (60%) Load

CRITICAL

THE DIFFERENCE IS LOAD!
The breaker above is the same breaker under variable loads!
Pro-Line's IEEE/ANSI load based standard shows this component's temperature rise
at about 240% of the maximum allowable rise, at any load current!


If your infrared testing company can't accurately analyze component problems,
how can you rely on their results?

Stop repairing non-problems and/or missing potentially severe problems. Let us show you how!