|
|
LOAD
IS THE KEY
Infrared
thermography is a valuable condition assessment tool for electrical
systems. However, the value of the technology is often short-circuited
by infrared electrical inspections that do not give appropriate
consideration to electrical load.
Most thermographers know that it is imperative to have the electrical
system under load during an infrared inspection. However, some thermographers
and the organizations that employ them believe that as long as they
can see some thermal energy emitting from the components, there
is sufficient load on the circuits.
But how much load is enough?
Without knowing the actual load, temperature measurement is mis-leading.
Without accurate temperatures, it is difficult, if not impossible,
to evaluate and classify the severity of the problem.
For example, the temperature of a specific anomaly on a circuit
loaded to only 20% of its rated capacity will be significantly lower
than if the circuit were carrying 70% of its rated load. This change
in electrical load would take the temperature level of the anomaly
from a low priority classification to an emergency situation. A
qualitative inspection can be performed without knowing the amount
of electrical load. However, the anomaly cannot be classified into
a repair priority and trending cannot be used. The maintenance response
to such a qualitative inspection is to correct every anomaly found
unless some exceptionally warm overall pattern was identified.
If thermographic inspections are being performed without taking
load readings, the thermographer must properly report that no attempt
was made to establish loads and that the temperature measurements
are not an accurate indication of the severity of the anomaly. In
other words, the thermographer must be honest and indicate the level
and accuracy of the inspection work. In a qualitative inspection,
no measurements are made; the thermal image is simply evaluated
to find an anomaly and identify where it exists.
The advantages of this approach are outlined in the accompanying
section: "Qualitative approach
to IR Electrical Inspection." The reason electrical load must
be measured to make an accurate diagnosis of an anomaly in an electrical
system is apparent form a review of basic electrical theory. The
relationship of current, voltage, and resistance is expressed in
Ohms Law. The amount of current in amperes flowing in a circuit
is equal to the difference in potential in volts divided by the
resistance in Ohms of the circuit. Ohms Law can be expressed by
the equation:I=E/R
Where:
I = Current, amps
E = Potential
R = Resistance, Ohms
The concepts of work, energy and power are also important to IR
electrical inspection. Work is the overcoming of resistance. Energy
is the ability to do work. Power is the rate of doing work or the
rate at which energy is expended. This relationship is illustrated
by the equation: Power = Work x time
The basic unit of electrical power is the watt (the product of voltage
and current), which represents the rate at any given instant at
which work is being done to move electrons through the circuit.
Electrical power is described by the equation: P=EI
Where:
P = Power, watts
E = Voltage, volts
I = Current, amps
Substituting the Ohms Law Equivalent of E, the power equation becomes:P=I2R.
Power gives an indication of the rate at which a device converts
electrical energy into another form of energy: such as heat, light,
or motion.
Using 2 Ohms of resistance for a loose electrical connection as
an example anomaly in a circuit loaded to 100 amps, power is calculated
to be 10 x 2 = 200 watts. If the resistance in the anomaly doubles
to 4 Ohms and current remains constant, power draw doubles to 400
watts of heating capacity. If current doubles to 20 amps and resistance
remains constant, power draw at the anomaly quadruples to 800 watts
of heating capacity. Since the electrical energy is being changed
quite efficiently, temperature will change accordingly. If the poor
condition continues to deteriorate and the load increases, temperature
will increase dramatically.
With this understanding, it is the author's opinion that all thermographers
must take a load reading at the time of inspection. Obviously there
are exceptions to the rule, but very few.
Along with load, the thermographers must consider a number of additional
parameters including:
Size and mass of component
Heat
transfer rates of conduction, radiation and convection
Size
of the target and distance
Importance
of component to the system or process
Calibration
of the infrared instrument
Ambient
fluctuations
Equipment
Cycling
Component
temperature rating and so on.
These subjects and many more are discussed at length in certification
courses on electrical thermography.
Click
here for a .PDF copy of this article
Please contact us for a free quote or an
on-site presentation.
Call our toll-free number 800-349-0055
or send us an email: click
here
Pro-Line Inspection
Services© 1982-2005
All Rights Reserved
|
|